Model | 15-SP07M-DC10 |
Test standard | IEC/ EN 61643-31 |
SPD type | T2 / Class II |
Max. PV voltage [ Uc pv ] | 1000V DC |
Nominal discharge current (8/20µs) | 20kA |
Maximum discharge current(8/20µs) | 40kA |
Poles | 3P |
Voltage protection level Up pv | 3.6kV |
Response time Ta | 25ns |
Connection wire specification | 4mm2(L/N); 6mm2(PE) |
Mounting | 35mm Din Rail |
Matched fuse or circuit breaker | 32A |
Type of remote signaling contact (Optional) |
C+NC: Normally closed C+NO: Normally open C: Common contact |
Max. Voltage/Current for remote signaling | 1A /2A /3A 125V AC |
Wiring for remote signaling | 1.5mm2 max. |
Operating temperature | -40°C to +80°C |
Shell material | UL94-V0 fireproof material |
FEATURES
- High discharge capacity, quick response, individually plugged modules
- Fast response time, din-rail installation
- Double thermal disconnection devices, provide more reliable protection
- Green window means normal, red means defect, need to change module
- Remote signaling contact optional
- T2 surge protection
- IEC/ EN 61643-31 certified
SPECIFICATION
Model | 15-SP07M-DC10 |
Test standard | IEC/ EN 61643-31 |
SPD type | T2 / Class II |
Max. PV voltage [ Uc pv ] | 1000V DC |
Nominal discharge current (8/20µs) | 20kA |
Maximum discharge current(8/20µs) | 40kA |
Poles | 3P |
Voltage protection level Up pv | 3.6kV |
Response time Ta | 25ns |
Connection wire specification | 4mm2(L/N); 6mm2(PE) |
Mounting | 35mm Din Rail |
Matched fuse or circuit breaker | 32A |
Type of remote signaling contact (Optional) |
C+NC: Normally closed C+NO: Normally open C: Common contact |
Max. Voltage/Current for remote signaling | 1A /2A /3A 125V AC |
Wiring for remote signaling | 1.5mm2 max. |
Operating temperature | -40°C to +80°C |
Shell material | UL94-V0 fireproof material |
DIMENSION